Hazardous Locations

This equipment is suitable for these locations:

Class I, Division 2 Groups A, B, C, D

Class I, Zone 2, Group IIC

Class II, Division 2 Groups F, G

Class III

Ordinary, nonhazardous locations only

The following statement applies to use in hazardous locations.

The terminals have a temperature code of T4 when operating in a 55 °C (131 °F)
maximum ambient temperature. Do not install the terminals in environments where
atmospheric gases have ignition temperatures less than 135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous locations.

Do not disconnect equipment unless power has been switched off and area is known to
be nonhazardous.

Do not connect or disconnect components unless power has been switched off.

All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section 18-1J2
as appropriate.

Peripheral equipment must be suitable for the location in which it is used.