High-bright Display Modules 17

Publication 2711P-IN026E-EN-P - September 2008

Earth/Ground Connection

PanelView Plus devices with a DC power input have an earth/ground terminal that
you must connect to a low-impedance earth/ground. The earth/ground connection
is on the rear of the display module.

The earth/ground terminal requires a minimum wire gauge.

On most PanelView Plus devices, the earth/ground terminal is internally connected
to the DC- terminal within the product.

The PanelView Plus devices have isolated and nonisolated communication ports.

For more information refer to the PanelView Plus Terminals User Manual,
publication

2711P-UM001

.

IMPORTANT

The earth/ground connection to ground is mandatory. This connection is required for
noise immunity, reliability, and Electromagnetic Compliance (EMC) with the European
Union (EU) EMC directive for CE-mark conformance. This connection is required for safety
by Underwriters Laboratory.

Earth/Ground Wire Specifications for DC Power

Attribute

Value

Symbol

GND

Wire Type

Stranded or solid, Cu 90 °C (194 °F)

Wire Gauge

14…10 AWG

Terminal Screw Torque

1.13…1.36 N•m (10…12 lb•in)

ATTENTION

Damage or malfunction can occur when a voltage potential exists between two separate
ground points. Make sure the terminal does not serve as a conductive path between
ground points at different potentials.