High-bright Display Modules 7

Publication 2711P-IN026E-EN-P - September 2008

USB Ports

The terminals contain universal serial bus (USB) ports that comply with hazardous
location environments. This section details the field-wiring compliance
requirements and is provided in accordance with the National Electrical Code,
article 500.

PanelView Plus 700 to 1500 Terminals Control Drawing

Selected nonincendive field wiring apparatus must have nonincendive circuit
parameters conforming with Table 2.

Table 1 - PanelView Plus 700 to 1500 USB Port Circuit Parameters

V

oc

I

sc

C

a

L

a

Groups A and B

Groups C and D

Groups A and B

Groups C and D

5.25V DC

1.68 A

10 µF

10 µF

15 µH

15 µH

Table 2 - Required Circuit Parameters for the USB Peripheral Device

V

max

V

oc

I

max

I

sc

C

i

+ C

cable

C

a

L

i

+ L

cable

L

a

USB

Peripheral

Device

Nonincendive Field
Wiring Apparatus

USB Port

Nonincendive Field Wiring

Associated Nonincendive Field Wiring Apparatus

PanelView Plus 700 to 1500 Host Product