Memory mapping, Field descriptions, Status indicators – Rockwell Automation 1797-OB4D FLEX Ex 24V DC Nonisolated Source 4 Output Module User Manual

Page 12

Advertising
background image

12 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Publication

1797-5.6 - June 2011

Memory Mapping

Status Indicators

Indicator

Status Description

Yellow

Individual input present

Flashing red

Channel fault

Solid red

Module did not pass power up check

Channel 0 is solid red while power-up check is running

Dec

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct

Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read 0

OVL

3

OVL

2

OVL

1

OVL

0

F3

F2

F1

F0

Write 0

Out

Enb

L

DA

3

DA

2

DA

1

DA

0

FS

3

FS

2

FS

1

FS

0

D3

D2

D1

D0

Configuration 1

RA

Alarm Filter

Ch 0…3

Where:

OVL = Overload alarm for individual channel

F = Fault alarm for individual channel

DA = Detect Alarms, Detection of Output faults (0 = Disable, 1 = Enable)

FS = Fault state (0 is reset and 1 is hold last state)

D = Data, Output data 0 = Off 1 = On

L = Latch alarms (0 = Disable, 1 = Enable)

Out Enb = Output Enable

RA = Reset Alarms (0 = Normal, 1 = Reset)

Field Descriptions

Field

Description

Fault Alarm

0 = No fault

1 = Wire-off fault or overload

100 Hz (10 ms) filter is integrated

Note: A wire-off fault or overload can be detected using this single bit.