FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 5

Publication

1797-5.6 - June 2011

6. Make certain that you only connect terminal base units to other

intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.

7. Remove the cap plug (4) and attach another intrinsically safe terminal

base unit to the right of this terminal base unit if required.

Installation in Zone 1

This module must not be exposed to the environment and must have a
suitable metal enclosure. It has a protection factor of IP20.

Installation on Zone 22

When the module is installed in Zone 22, the following cabinets must be used:
IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. These
cabinets can be purchased from:

Pepperl+Fuchs GmbH

Lilienthalstrasse 200

68307 Mannheim, Germany

Attn: PA Sales Dept.

Kirsten Becker

Telephone +49 776 1298

www.pepperl-fuchs.com

WARNING

This module cannot be used in an intrinsically safe environment after it has
been exposed to nonintrinsically safe signals.