Rockwell Automation 1797-OB4D FLEX Ex 24V DC Nonisolated Source 4 Output Module User Manual

Page 16

Advertising
background image

16 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Publication

1797-5.6 - June 2011

Power supply

(+V, -V Intrinsically safe)

U

i

< 9.5V DC

I

i

< 1 A

L

i

= Negligible

C

i

= Negligible

Module field-side
power consumption

7.5 W

Power dissipation

5 W

Thermal dissipation

17.07 BTU/hr

Module location

1797-TB3 or 1797-TB3S Terminal base unit

Conductors wire size, max

4 mm

2

(12 gauge) stranded

1.2 mm (3/64 in.) insulation

Dimensions

HxWxD

46 x 94 x 75 mm

(1.8 x 3.7 x 2.95 in.)

Weight, approx.

200 g (7.05 oz.)

Keyswitch position

7

Environmental Specification

Attribute

Value

Temperature, operating

-20…+70

°

C (-4…+158

°

F)

Temperature, storage

-40…+85

°

C (-40…+185

°

F)

Relative humidity

5…95% noncondensing

Shock, operating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Shock, nonoperating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Vibration

Tested 2 g @ 10…500 Hz per IEC68-2-6

General