4 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Publication

1797-5.6 - June 2011

Install the Module

This module must be used with a 1797-TB3 or 1797-TB3S intrinsically safe
terminal base unit.

1. Rotate keyswitch (3) on terminal base unit (5) clockwise to position 7

as required for this type of module.

Do not change the position of the keyswitch after wiring the
terminal base unit

2. Make certain the FlexBus connector (1) is pushed all the way to the

left to connect with the neighboring terminal base/adapter.

You cannot install the module unless the connector is fully
extended.

3. Make sure the pins on the bottom of the module are straight so they

will align properly with the connector in the terminal base unit.

4. Position the module (8) with its alignment bar (7) aligned with the

groove (6) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit.

The module is seated when the latching mechanism (2) is locked into
the module.

ATTENTION

This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR Publication 11. Without appropriate precautions, there may be
potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that
will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The interior of the enclosure must be accessible
only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required
to comply with certain product safety certifications.

Advertising