Ul, c-ul i/o entity parameters – Rockwell Automation 1797-OB4D FLEX Ex 24V DC Nonisolated Source 4 Output Module User Manual

Page 20

Advertising
background image

20 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Publication

1797-5.6 - June 2011

The values of L

o

and C

o

listed in the table above are allowed if one of the

following conditions is met:

• The total L

i

of the external circuit (excluding the cable) is < 1% of the

L

o

value or

• The total C

i

of the external circuit (excluding the cable) is < 1% of the

C

o

value.

The values of L

o

and C

o

listed in the table above shall be reduced to 50%

when both of the following conditions are met:

• The total L

i

of the external circuit (excluding the cable) is ≥ 1% of the

L

o

value and

• The total C

i

of the external circuit (excluding the cable) is ≥ 1% of the

C

o

value.

Note: The reduced capacitance of the external circuit (including cable) shall
not be greater than 1µF for IIB and IIA and 600nF for IIC.

UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated,
tested, and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus

for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations

Entity Parameters

Protection Group

Allowed
Capacitance

Allowed
Inductance

1797-OB4D

U

o

= 27.4V

I

o

= 110 mA

Ex ia

IIB

677 nF

8 mH

IIC

87 nF

2 mH

If concentrated capacitance
and/or inductance are available,
use the following values.

Ex ia

IIB

150 nF

5 mH

IIC

30 nF

2 mH