52 Interpret Status Indicators

Chapter Summary

This appendix described how to troubleshoot your adapter module by
interpreting the status indicators.

Module Status Indicator

Off

No power. Adapter does not have 24V DC
power. Make sure power is being supplied to
the adapter.

Flashing green

Standby. Adapter not configured. Configure
adapter.

Green

Operational. Adapter operating correctly. No
action required.

Flashing red

Minor fault. A recoverable fault has been
detected. This could be caused by an incorrect
or inconsistent configuration.
Check configuration and reconfigure as
needed.

Solid red

Major fault. An unrecoverable fault has been
detected. Recycle power to the adapter. If this
does not clear the fault, replace the adapter.

Flashing red/green

Self test. Adapter performing power-up self
test. Wait until completed.

Network Status Indicator

Off

Not powered. No IP address. Adapter is not
powered or does not have an IP address.
Verify there is power and the adapter is
correctly wired to the power supply.
Make sure the adapter is configured.

Flashing green

No connection. Adapter has obtained an IP
address, but has no established connections.

Green

CIP connections. Adapter has an IP address
and at least one established connection.

Flashing red

Connection timeout. One or more of the
connections in which the adapter is the target
has timed out.

Red

Duplicate IP address. Adapter has detected
that its IP address is already in use. Configure
the adapter with a unique IP address.

Flashing red/green

Self-test. Adapter performing power-up self
test.