Work with the configuration pages – Rockwell Automation 1794-AENTR_AENTRXT FLEX I/O Dual Port EtherNet/IP Adapter Modules User Manual

Page 76

Advertising
background image

Publication 1794-UM066A-EN-P - February 2012

68 Adapter Web Dialogs

• Received / Transmitted packets
• Connection ID
• Source
• Destination
• Multicast Address
• RPI
• Lost Packets
• Size

Work with the
Configuration Pages

To work with the Configuration pages, follow these procedures.

1. From the Home page, click Configuration or Expand to see the

Configuration options, if needed.

2. From the Configuration page, click one of the following:

• Identity
• Network
• Services

IMPORTANT

The values on these pages are in non-volatile memory. Changes to these
parameters do not take effect until you reset or cycle power through the
FLEX I/O adapter.

IMPORTANT

If you set the value of the adapter switch to 888 and then power cycle the
module, the following occurs:

The DHCP Enabled function is enabled (set to True).

The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.

The web server is enabled. The Disabled Web Server function is
disabled.

The Ethernet port are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.

The password for this page resets to the factory default which is
"<blank>".

Note the value of the switches before you enter the 888 value because
you must return the adapter to those values once this process is
complete.