Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 262

262
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
Chapter 4
Commissioning
•
Capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.
•
Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
•
Save the worksheet as “Drift @ 15 Degree Lead Angle”, for example.
Table 18 - Oscilloscope Setting
Figure 218 - Sample Waveforms
Synchronous Transfer Test to verify Sync Lead Angle (50Hz System)
Ch1: Idc1 (yellow), Ch2: Vuv (blue), Ch3: Vuvs (red)
While performing a live synchronous transfer:
•
Capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.
•
Capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.
•
Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
•
Save the worksheet as “Synch on Motor 01”, for example.
Table 19 - Oscilloscope Setting
Oscilloscope
Time Base
Waveform
Test-Point
Waveform Label
Ch. 1
10ms/div.
DC Link Current
Idc1
Idc1
Ch. 2
Motor Voltage
Vuv
Vuv
Ch. 3
Bypass Line Voltage
Vuvs
Vuvs
Oscilloscope
Time Base
Waveform
Test-Point
Waveform Label
Ch. 1
10ms/div.
DC Link Current
Idc1
Idc1
Ch. 2
Motor Voltage
Vuv
Vuv
Ch. 3
Bypass Line Voltage
Vuvs
Vuvs