Terminal / connections descriptions – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 324

324
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
Chapter 5
Component Definition and Maintenance
Terminal / Connections Descriptions
The terminal connections are shown in
.
Figure 271 - Terminal locations on AC/DC Pioneer power supply
Ensure the output of the supply is 56V DC.
There is a potentiometer on the top of the power supply that adjusts the 56 Volt
DC output for the power supply. Isolate the output of the power supplies;
multiple supplies in series will affect your measurements. With the control power
on and the output of the AC/DC Converter isolated from the drive control,
adjust the potentiometer until the output equals 56 volts DC. Perform this test
on each power supply. When all adjustments are complete, reconnect the power
supply to the circuit and remeasure the output. Readjust if necessary.
If it is not possible to maintain 56 V DC, the power supply may be faulty.
P1-AC input
PIN#
LABEL
1
EARTH
2
LINE
3
NEUTRAL
P2-DC output
PIN#
LABEL
1
+56V
2
+56V COMM
3
+56V
4
+56V COMM
P3-FAIL output
PIN#
LABEL
3
DC POWER FAIL (OUTPUT POWER
GOOD)
15
CURRENT SHARING
14
DC POWER FAIL COMMON
Control signals
DC outputs
Single phase input
TOP
VIEW
FRONT VIEW
Ea
rt
h
Li
ne
Ne
u
tr
a
l