Chapter 2
Drive Installation
Power Connections
The installer must ensure that interlocking with the upstream power source has
been installed and is functioning.
The installer is responsible for ensuring that power connections are made to the
equipment in accordance with local electrical codes.
The drive is supplied with provision for cable lugs. The power terminals are
identified as follows:
Incoming Connections
•
Drives with AFE Rectifiers:
2U, 2V, 2W
•
Drives with 18 Pulse Rectifiers
–
Secondary (d0)
2U, 2V, 2W
–
Secondary (d-20)
3U, 3V, 3W
–
Secondary (d+20)
4U, 4V, 4W
•
Motor Connections
U, V, W
The installer is responsible for ensuring that power connections are made with
appropriate torque. (Refer to
Torque Requirements for Threaded Fasteners on
.)
The drive is supplied with provision for grounding of cable shields and stress
cones near the power terminals.