Connect dc power – Rockwell Automation 2711-L6Cxx_B6Cxx PanelView 600 Terminals Installation Instructions User Manual
Page 12

12 PanelView 600 Terminals
Publication 2711-IN010G-EN-P - February 2009
3. Apply power to the terminal.
Connect DC Power
The L1 versions of the PanelView 600 terminal (catalog number 2711-K6C1L1,
2711-B6C1L1) connect to a 24V DC power source.
The electrical ratings for the PanelView 600 are shown below. Electronic circuitry
and an internal fuse protect the terminal from reverse polarity and over–voltage
conditions.
Terminal Type
Supply Voltage
Power Consumption
PV600
18…32V DC,
(24V DC nominal)
24 Watts maximum
(1.0 Amps @ 24V DC)
ATTENTION
For DC powered units, use a Class 2/SELV (Safety Extra-Low Voltage), isolated and
ungrounded power supply as input power to the terminals. This power source provides
protection so that under nominal and single fault conditions, the voltage between
conductors and between conductors and Functional Earth/Protective Earth does not
exceed a safe value.
L1 L2
Black (line)
White
(neutral)
Green
L1 L2
Brown (line)
Green
(earth ground)
Green/Yellow
(protective earth)
Blue
(neutral)
120/240V AC, 3 Wire,
U.S. Color Code
120/240V AC, 3 Wire, European
Harmonized Color Code
Power Terminal
Block (fixed)
To Power Source
To Power Source