Connect dc power – Rockwell Automation 2711-L6Cxx_B6Cxx PanelView 600 Terminals Installation Instructions User Manual

Page 12

Advertising
background image

12 PanelView 600 Terminals

Publication 2711-IN010G-EN-P - February 2009

3. Apply power to the terminal.

Connect DC Power

The L1 versions of the PanelView 600 terminal (catalog number 2711-K6C1L1,
2711-B6C1L1) connect to a 24V DC power source.

The electrical ratings for the PanelView 600 are shown below. Electronic circuitry
and an internal fuse protect the terminal from reverse polarity and over–voltage
conditions.

Terminal Type

Supply Voltage

Power Consumption

PV600

18…32V DC,
(24V DC nominal)

24 Watts maximum
(1.0 Amps @ 24V DC)

ATTENTION

For DC powered units, use a Class 2/SELV (Safety Extra-Low Voltage), isolated and
ungrounded power supply as input power to the terminals. This power source provides
protection so that under nominal and single fault conditions, the voltage between
conductors and between conductors and Functional Earth/Protective Earth does not
exceed a safe value.

L1 L2

Black (line)

White
(neutral)

Green

L1 L2

Brown (line)

Green
(earth ground)

Green/Yellow
(protective earth)

Blue
(neutral)

120/240V AC, 3 Wire,
U.S. Color Code

120/240V AC, 3 Wire, European
Harmonized Color Code

Power Terminal
Block (fixed)

To Power Source

To Power Source