Rockwell Automation 2711-L6Cxx_B6Cxx PanelView 600 Terminals Installation Instructions User Manual
Page 13
PanelView 600 Terminals 13
Publication 2711-IN010G-EN-P - February 2009
To connect DC power to the PV600 terminal:
1. Secure the DC power wires to the DC Negative and DC Positive screws on
the terminal block.
2. Secure the Earth Ground wire to the
screw on the terminal block.
3. Apply 24V DC power to the terminal.
ATTENTION
•
Do not connect the PanelView terminal to an AC power source. Connecting to an AC
power source may damage the terminal.
•
The PanelView 600 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
WARNING
Explosion Hazard - Do not connect or disconnect equipment while circuit is live
unless area is known to be non-hazardous.
ATTENTION
Do not apply power to the terminal until all wiring connections have been made.
Failure to do so may result in electrical shock.
+
Earth Ground
DC Negative
DC Positive
Power Terminal
Block (fixed)