Fiber optic cable attenuation measurements, Cable attenuation measurement – Rockwell Automation 2090-xxx Fiber Optic Cable Installation and Handling Instructions User Manual

Page 8

Advertising
background image

8 Fiber Optic Cable Installation and Handling Instructions

Publication 2090-IN010C-EN-P – April 2005

Fiber Optic Cable Attenuation Measurements

1. Inspect and clean the ends of the reference cable.

2. Securely connect appropriate reference cable corresponding to the

type of cable to be tested.

• POF reference cable used for testing POF cable
• HCS reference cable used for testing HCS cable

Figure 7 Zero dB Reference

3. Turn on light Source

4. Turn on optometer and select appropriate wavelength.

5. Verify Output Power

a. POF reference cable -7.5dBM to -3.5dBM
b. HCS reference cable -18dBM to -10dBM

Note: If output power is out of range, verify that the source has fresh
batteries and proper calibration.

6. Set the zero db reference for the optometer. (see optometer

reference manual)

Cable Attenuation Measurement

1. Inspect ends of cable for proper termination. Clean ends of fiber.

2. Turn on light Source

LED Light Source
650nM nominal

Optometer Set to 0dB
reference

1 meter reference

Advertising