Power wiring requirements – Rockwell Automation 2097-Vxxxx Kinetix 300 EtherNet/IP Indexing Servo Drive Installation Instructions User Manual

Page 12

Advertising
background image

12 Kinetix 300 EtherNet/IP Indexing Servo Drive

Rockwell Automation Publication 2097-IN001I-EN-P - July 2013

Shunt Resistor and DC Bus (BC) Pinout

Motor Power (MP) Pinout

Safe Torque Off (STO) Pinout

The Kinetix 300 drives ship with the safe torque-off circuitry enabled. Connect the safe
torque-off inputs to a safety circuit or install motion-allowed jumpers to obtain motion. Refer to
the Kinetix 300 EtherNet/IP Indexing Servo Drives User Manual, publication

2097-UM001

, for

details.

Power Wiring Requirements

Wire must be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is
arbitrary and earth-ground connection is required for safe and proper operation.

BC Designator

Description

Signal

+

Positive DC bus and shunt resistor

+

+

+

SH

Shunt resistor

SH

Negative DC bus

MP Designator

Description

Signal

PE

Protective earth (ground)

PE

W

Motor power out

W

V

Motor power out

V

U

Motor power out

U

STO Pin

Description

Signal

1

+24V DC output from the drive

+24V DC Control

2

+24V DC output common

Control COM

3

Safety status

Safety Status

4

Safety input 1 (+24V DC to enable)

Safety Input 1

5

Safety common

Safety COM

6

Safety input 2 (+24V DC to enable)

Safety Input 2

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the values and
methods provided.