14 Kinetix 300 EtherNet/IP Indexing Servo Drive

Rockwell Automation Publication 2097-IN001I-EN-P - July 2013

Ground Your Kinetix 300 Drive to the Subpanel

If the Kinetix 300 drive is mounted on a painted subpanel, ground to a bonded cabinet-ground
bus with a braided ground strap or 4.0 mm

2

(12 AWG) solid-copper wire, 100 mm (3.9 in.) long.

Connecting the Braided Ground Strap

For dimensions, see

Kinetix 300 Drive Mounting Dimensions

on

page 6

.

ATTENTION: To avoid personal injury and equipment damage, make sure

Installation complies with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline
provisions for safely installing electrical equipment.

Motor power connectors are used only for connection purposes. Do not use motor power
connectors to turn the unit on and off.

Shielded power cables are grounded to prevent potentially high voltages on the shield.

Bonded Cabinet
Ground Bus

Ground Grid or Power
Distribution Ground

Braided

Ground Strap

Ground Stud