Control Drawing - Class I Division 2 and Zone 2

The following control drawing is provided in accordance with the National
Electrical Code, Article 500 (Class I, Division 2, Groups A, B, C, D and Class I,
Zone 2, Group IIC).

1200P Control Drawing for National Electrical Code

VersaView 1200P USB and PS2 Port Circuit Parameters

Parameter

Value

Parameter Definition

V

oc (USB)

V

oc (PS2)

5.25V dc

Open circuit voltage of each host USB or PS2 port.

I

sc (USB)

1.0 A

Maximum output current of each host USB port.

I

sc (PS2)

2.1 A

Maximum output current of the host PS2 port.

C

a (USB)

20 µF

This value is the maximum total capacitance that can be
connected to each USB port when used singly or together.
The total capacitance of each USB peripheral and its cable
must not exceed the indicated value.

C

a (PS2)

20 µF

This value is the maximum total capacitance that can be
connected to a single PS2 port when used alone, or the sum
of the total capacitance connected to both PS2 ports when
used simultaneously. If multiple PS2 peripheral devices are
used, the total capacitance of all devices and their cables
must not exceed the indicated value.

L

a (USB)

L

a (PS2)

3.11 µH

This value is the maximum total inductance that can be
connected to each USB and PS2 port. The total inductance
of each peripheral device and its cable must not exceed the
the indicated value.

VersaView 1200P Host Product

USB Port

PS2 Keyboard Port

PS2 Mouse

PS2 Keyboard

Associated Nonincendive

Field Wiring Apparatus

Nonincendive

Field Wiring Apparatus

USB Peripheral Device

USB Peripheral Device