Mounting Clearances
Allow adequate space around the computer for mounting, air flow, and
maintenance. The figure below shows recommended minimum clearances to other
components within the rack or enclosure.
Mounting Clearances
ATTENTION
Do not operate this computer within a confined space using clearances
that are less than those show below unless adequate ventilation or other
cooling methods are used to lower the air temperature within the
enclosure.
Top Clearance
50 mm (2 in.) for air flow
Right Side Clearance
50 mm (2 in.) for air flow
Bottom Clearance
102 mm (4 in.) for air flow
and connections
Left Side Clearance
50 mm (2 in.) for air flow
Back Clearance
25 mm (2 in.)