To prevent thermal overload of the Braking Unit, it must operate within
the following limits:

In a time range of 10 minutes the permissible loading must be limited
to the maximum peak current of the DBU (300A) up to a maximum of
2.5 minutes.
This maximum current-time area of 750 Amp.-minutes can be of any
shape, as long as 300A is not exceeded.

The peak current (I

Peak

) in the following two examples is 300 Amp

(maximum current with R

min

= 3.2 ohm at 600 VAC line) and the

current-time area also meets the 750 Amp.-minutes requirement.

Figure P.4 Examples for Permissible Loading of the DBU

Permissible Loading of the DBU

1) Linear deceleration to zero speed of

a drive with high inertia connected
(e.g. centrifuge)

2) Drive with active load

(e.g. crane)

Current-time area:

(300 * 5) / 2 = 750 Amp-Min.

Current-time area:

(300 * 1) + (112.5 * 4) = 750 Amp-Min.

5

10

I

Peak

minutes

t

300A

0

4

10

I

Peak

112.5A

t

minutes

1

300A

0