Power and control terminals, Table 1.b, Figure 1.3 – Rockwell Automation AK DBU - Dynamic Braking Unit 600/690 VAC User Manual

Page 19

Advertising
background image

Installation/Wiring

1-7

Power and Control Terminals

Figure 1.3 Location of Power Connections and Control Terminals

for Customer Wiring (Front View Shown)

Table 1.A Power Terminals

Table 1.B Power Terminal Specifications

No.

Description

Notes

BR1

DC Brake (+)

Brake Resistor Connection (+)

BR2

DC Brake (-)

Brake Resistor Connection (-)

DC+

DC Bus (+)

DC Bus Connection (+)

DC-

DC Bus (-)

DC Bus Connection (+)

PE

Protective Earth

10/11 Thermostat N.C. contact For control terminals see

Figure 1.4

No. Description

Wire Size Range

(1)

(1)

Max./Min. sizes the terminals will accept - these are not recommendations.

Torque

Maximum Minimum

Maximum

Recommend

Power Connections
Bus Bars with Bolts M10

95 mm

2

(4/0 AWG)

10 N-m
(89 lb.-in)

10 N-m
(89 lb.-in)

PE
Bolt M10

50 mm

2

(6 AWG)

50 mm

2

(AWG)

10 N-m
(89 lb.-in)

10 N-m
(89 lb.-in)

Thermostat N.C. contact and
Fan Supply Terminal

For control terminal specifications see

Table 1.C

PE

BR2

DC-

DC+ BR1