Power and control terminals, Table 1.b, Figure 1.3 – Rockwell Automation AK DBU - Dynamic Braking Unit 600/690 VAC User Manual
Page 19

Installation/Wiring
1-7
Power and Control Terminals
Figure 1.3 Location of Power Connections and Control Terminals
for Customer Wiring (Front View Shown)
Table 1.A Power Terminals
Table 1.B Power Terminal Specifications
No.
Description
Notes
BR1
DC Brake (+)
Brake Resistor Connection (+)
BR2
DC Brake (-)
Brake Resistor Connection (-)
DC+
DC Bus (+)
DC Bus Connection (+)
DC-
DC Bus (-)
DC Bus Connection (+)
PE
Protective Earth
10/11 Thermostat N.C. contact For control terminals see
No. Description
Wire Size Range
(1)
(1)
Max./Min. sizes the terminals will accept - these are not recommendations.
Torque
Maximum Minimum
Maximum
Recommend
Power Connections
Bus Bars with Bolts M10
95 mm
2
(4/0 AWG)
10 N-m
(89 lb.-in)
10 N-m
(89 lb.-in)
PE
Bolt M10
50 mm
2
(6 AWG)
50 mm
2
(AWG)
10 N-m
(89 lb.-in)
10 N-m
(89 lb.-in)
Thermostat N.C. contact and
Fan Supply Terminal
For control terminal specifications see
PE
BR2
DC-
DC+ BR1