Mounting instructions, Cabinet mounted drives (see figure b.2) – Rockwell Automation AK DBU - Dynamic Braking Unit 600/690 VAC User Manual

Page 33

Advertising
background image

CE Conformity

B-3

Cabinet Mounted Drives

(see

Figure B.2

)

If the drive related components are mounted in a cabinet, the following
rules must be observed:

• If located in a common cabinet, all drive related components must be

screwed directly to a blank (non painted) panel with good
conductivity and the largest possible contact area.

• The support panel for the DBU and an inverter with filters must be a

conducting steel sheet with a common ground bus bar located at the
bottom of the support panel. This ground bus bar, must be solidly
connected to the panel to ensure good conductivity.

• All cable screens for cables entering the cabinet must be solidly

connected to the cabinet’s ground bus bar or to the ground stud of the
inverter with a large connection area and good conductivity to ensure
that the grounding represents a low impedance for HF signals.

• Either galvanized cable brackets or EMC cable glands are required.

Standalone Drives and Related Components

(see

Figure B.3

)

• If the drive and related components (inverter, RFI-Filter, DBU and

brake resistor) are mounted in separate enclosures, these must be of
conductive metallic material in which the diameter of ventilation
holes should not exceed 6 mm (0.24 in).

• The spacing between brake resistor assembly and the enclosure wall

shall be 100 mm (4 in) minimum.

Mounting Instructions

Advertising