Appendix a, Specifications, Aspecifications – Rockwell Automation AK DBU - Dynamic Braking Unit 600/690 VAC User Manual

Page 27: Appendix

Advertising
background image

Appendix

A

Specifications

This appendix provides electrical, environmental, functional and
physical specifications for the DBU and the diagnostic card BUB.

For information on…

See

page

For information on…

See

page

DBU

A-1

Brake Resistor Specifications

A-4

Dimensions

A-3

Fuse Ratings

A-4

Diagnostic Card BUB

A-4

DBU

Specifications

Power Ratings
Input Voltage

600V

690V

Peak Braking Power

268 kW

305 kW

Minimum Brake Resistor Value permitted

for Peak Braking Power

3.2 ohm

3.7 ohm

Max. Peak Braking Current with 150sec ON

time at up to 25% duty cycle

300 Amp

Maximum Mean RMS Braking Current

150 Amp

Heat Dissipation (Average) at 25% duty cycle

170 W

Power consumption of the control circuits

27mA

Maximum DC bus Voltage

at terminals DC+,DC-

DC 1150V

Pulse width modulation PWM,

switching frequency

0.67 kHz

Capacitance of the built-in snubber

4

µF

Control Output Specifications
Heat sink temperature sensor

The temperature sensor trips if heat sink

temperature exceeds maximum

temperature.

NC contact output rating (max.)

Resistive Rating: 15A at 125V AC,

10A at 250V AC,

7A at 24V DC

Inductive Rating: 10A at 125V AC,

6A at 250V AC

Advertising