2-4

Start Up / Troubleshooting

Table 2.A Possible Faults and Corrective Actions

Troubleshooting

Fault

Cause

Corrective Action

Heat sink Over
Temperature

Heat sink temperature
exceeds maximum
rating.

1. Verify the maximum ambient temperature

has not been exceeded.

2. Check fan for correct operation.

Replace fan if necessary with fan kit
No. SK-D9-FAN1

3. Check for excess load on the DBU.

Refer to

Appendix C

for calculations.

Verify the braking duty cycle does not
exceed the drive(s) design specification.

4. Check for proper clearance around the

DBU.

5. Contact your local RA sales office.

DC Output
Voltage Loss

Loss of DC Bus Power 1. Check 3-Phase AC Incoming Power on the

drive(s) for undervoltage or phase loss.

2. Check Fuses on DC bus input leads.
3. Check Inverter.
4. Contact your local RA sales office