Recommendations for the selection and wiring of the control cables:

• Cable must have copper conductors only.
• Cable with 600V rating or greater is required.
• Control cables outside the cabinet should be separated from power

cables by at least 0.3 meters (1 foot).

Figure 1.4 Input Control Terminals

Table 1.C Input Control Terminal Specifications

Drive(s) Run Interlock

In order to protect the DBU from an overtemperature condition, the
normally closed contact (DBU Overtemperature - terminals 10 and 11)
must be connected in series with a resistor thermostat to an AC-line
input contactor to ensure the drives are stopped if an overtemperature
condition occurs either in the DBU or the Brake Resistor.
See

Appendix A

for contact ratings.

Control Wiring

No.

Connection

Wire Size Range

(1)

(1)

Max./Min. sizes the terminals will accept - these are not recommendations.

Torque

Maximum Minimum

0, 115 Fan Supply, 115V AC

4 mm

2

(11 AWG)

0.5 mm

2

(22 AWG)

0.8 Nm
(7 lb.-in.)

10, 11 Thermostat NC Output Contact,

Opens at power stack over temperature

Thermostat N.C. output contact

Fan Supply Input Terminals

11
10
115
0

!

ATTENTION: The DBU and the drive(s) do not offer protection for
externally mounted brake resistors. Risk of fire exists if the brake
resistors are not protected. Resistor packages must be self-protected
from overtemperature or a circuit equivalent to the one shown in

Figure

1.5

must be supplied.