Rockwell Automation 4100-IF2 IF2 I/O Interface to PDM Installation Instructions User Manual

Page 9

Advertising
background image

IF2 I/O Interface to PDM 9

Publication 4100-IN001A-EN-P- February 2001

3. Using a small, flat-head screwdriver, turn the clamping screw

counter-clockwise several times.

4. Using a proper stripping tool, strip the wire insulation back on

the cable lead.

5. Trim the cable lead so that 0.275 inches of metal wire is

exposed.

6. Insert the cable lead in the appropriate terminal. Refer to the

proper figures for their locations.

7. Use the screwdriver to tighten the clamping screw to the

proper torque (0.25 N-m/2.2 in-lb.).

8. Verify that the cable lead does not pull out of the terminal.

9.

The function of these connectors, their pinouts, and names are
defined in the following sections.

Open

Go to step 4

IMPORTANT

All terminals accommodate a maximum of 14 gauge
wire.

If the cable lead:

Do this:

Pulls out of the terminal

Repeat steps 3 through 9 again

Does not pull out of the terminal

Repeat steps 3 through 9 for the
next terminal

If the terminals are:

Do this: