Connecting DC Power

All of the PV550/600 touch screen terminals (e.g., Catalog No. 2711-T5A1L1 or
2711-T6C8L1) connect to a 24V DC power source.

The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions.

Terminal Type

Supply Voltage

Power Consumption

PV550 Touch

18…2V DC,
(24V DC nominal)

18 Watts max. (0.75 Amps @ 24V DC)

PV600 Touch

18…32V DC,
(24V DC nominal)

24 Watts max. (1.0 Amps @ 24V DC)

ATTENTION

Do not connect the PanelView terminal to an AC power source. Connecting to an AC
power source may damage the terminal.

ATTENTION

The PanelView 550/600 terminal is designed for safe use when installed in a
suitably rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.

ATTENTION

Use only a Safety Extra Low-Voltage (SELV) power supply as a source for the
PanelView 550/600 terminal. A SELV power supply does not exceed 42.4V DC.