Hazardous location considerations – Rockwell Automation 2711-T5AxxL1_T6CxxL1 PanelView 550/600 Touch Screen Terminals User Manual

Page 3

Advertising
background image

PanelView 550/600 Touch Screen Terminals 3

Publication 2711-IN034

F-EN-P - February 2009

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class II,
Division 2, Groups F, G; Class III, Division 2; or non-hazardous locations only. The
following WARNING statement applies to use in hazardous locations.

See the nameplate on terminal for hazardous locations certifications.

The following PV550 terminals have an operating temperature code of T2
(maximum operating temperature of 300

°

C or 572 °F).

touch screen only terminals (series A)

Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 300 °C (572 °F).

The following PV550 following PV550 terminals have an operating temperature
code of T4 (maximum operating temperature of 135 °C or 275 °F).

touch screen only terminals (series B and later)

Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 135 °C (275 °F).
The PanelView 600 touch screen terminals have an operating temperature code of
T4 (maximum operating temperature of 135

°

C or 275

°

F). Do not install the

terminals in environments where atmospheric gases have ignition temperatures less
than 135

°

C (275

°

F).

WARNING

EXPLOSION HAZARD

Substitution of components may impair suitability for Class I, Class II, Class III
Division 2.

Do not replace components or disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.

Do not connect or disconnect components unless power has been switched off
or the area is known to be non-hazardous.

This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.

All wiring must comply with N.E.C. article 501-4(b), 502-4(b), 503-3(b) as
appropriate.

ATTENTION

In Class 1, Class II, Class III, Division 2 Hazardous locations, the PanelView 550
terminal must be wired per the National Electric Code as it applies to hazardous
locations. Peripheral equipment must also be suitable for the location in which it is
installed.