Wiring and Safety Guidelines

Install the PanelView 550/600 touch screen terminal using publication 70E,
Electrical Safety Requirements for Employee Workplaces. In addition to the NFPA
general guidelines, follow these recommendations:

Route incoming power to the PanelView 550/600 terminal by a separate path
from the communications cable.

Where power and communication lines must cross, they should cross at
right angles. Communications lines can be installed in the same conduit as
low level DC I/O lines (less than 10 Volts).

Grounding minimizes noise from Electromagnetic Interference (EMI) and is
a safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.

A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.

Enclosures

Mount the PanelView 550/600 touch screen terminal in a panel or enclosure to
protect the internal circuitry. The terminal meets NEMA Type 12/13 and 4X (indoor
use) ratings only when properly mounted in a panel or enclosure with the
equivalent rating.

Allow enough space within the enclosure for adequate ventilation. Consider heat
produced by other devices in the enclosure. The ambient temperature around the:

PV550 terminal must be between 0…55

°

C (32…131

°

F).

PV600 terminal must be between 0…50

°

C (32…122

°

F).

Make provisions for accessing the back panel of the terminal for wiring,
maintenance, installing a memory card, and troubleshooting.