Out-of-range detection, Installation planning – Rockwell Automation T743x-xx ICS Regent+Plus RTD Input Equipment User Manual
Page 15
 
RTD Input Equipment (T7432)
 
P D - 7 0 3 7 M a r - 0 6  
15
Table 1. Temperature Data Ranges.
Out-of-Range Detection
When the RTD measures temperatures outside of the 
operating range listed in Table 1, the signal is considered to 
be out-of-range. The RTD equipment will continue to provide 
over-range and under-range readings up to the minimum and 
maximum readings shown in the Table. 
Also, many open-circuit and short-circuit wiring faults will 
cause out-of-range conditions for RTD inputs. In these cases, 
the temperature data value is the minimum or maximum 
value shown in the Table. 
When the signal is out-of-range, the NOSIG bit for the RTD 
input is set. In application programming, the NOSIG contact 
in ladder logic can be used to sense the RTD out-of-range 
condition. For more information, see Programming, starting 
on page 23. 
Installation Planning
Accuracy Considerations
Use the following guidelines to maximize overall system 
accuracy: