RTD Input Equipment (T7432)


2 6

Industrial Control Services

Common Mode Rejection

100 dB @ 50/60 Hz

60 dB minimum, elsewhere

Normal Mode Rejection

70 dB typical

Termination Panel Cable
Length

Maximum 50 cable feet
(15 m)

Isolation

2500 volts minimum (Mux to
input module)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Safety

Pending certification to DIN
V VDE 0801 for Risk Class 5.
Also designed to meet UL
508 and CSA 22.2, No. 142-
M1981

Heat Dissipation

Input module:

Termination panel/Mux:


4.5 Watts, 15 BTUs/hour
2.5 Watts, 9 BTUs/hour

Dimensions

Input Module

Height:

Width:

Depth:

Termination Panel

Height:

Width:

Depth (with MUX):



12.6” (320 mm)
1.27” (32 mm)
10.125” (257 mm)

6.94” (176 mm)
19.0” (483 mm)
5.12” (130 mm)

Weight

Input module:

Mux:

Termination panel:


3.5 lbs (1.6 kg)
2 lbs (0.9 kg)
5.6 lbs (2.5 kg)