Rockwell Automation T743x-xx ICS Regent+Plus RTD Input Equipment User Manual
Page 26
 
RTD Input Equipment (T7432)
 
2 6  
Industrial Control Services
Common Mode Rejection
100 dB @ 50/60 Hz
60 dB minimum, elsewhere
Normal Mode Rejection
70 dB typical
Termination Panel Cable 
Length 
Maximum 50 cable feet 
(15 m) 
Isolation
2500 volts minimum (Mux to 
input module) 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity, 
non-condensing 
Safety
Pending certification to DIN 
V VDE 0801 for Risk Class 5. 
Also designed to meet UL 
508 and CSA 22.2, No. 142-
M1981 
Heat Dissipation
Input module:
Termination panel/Mux:
 
4.5 Watts, 15 BTUs/hour 
2.5 Watts, 9 BTUs/hour 
Dimensions
Input Module
Height:
Width:
Depth:
Termination Panel
Height:
Width:
Depth (with MUX):
 
 
12.6” (320 mm) 
1.27” (32 mm) 
10.125” (257 mm) 
 
6.94” (176 mm) 
19.0” (483 mm) 
5.12” (130 mm) 
Weight
Input module:
Mux:
Termination panel:
 
3.5 lbs (1.6 kg) 
2 lbs (0.9 kg) 
5.6 lbs (2.5 kg)