RTD Input Equipment (T7432)


P D - 7 0 3 7 M a r - 0 6

5

how to address that module and its points specifically. If a
module is removed, or is replaced with a module of a different
type, the processor modules will indicate an I/O module error.

Loopback logic tests periodically write data to the module and
then read it back to determine whether the module’s I/O bus
interface logic is functioning correctly.

Multiplexer Testing

The serial communications link to the RTD Mux is
continuously monitored. Additionally the data received from
the Mux is checked for proper data format, parity and numeric
range reasonableness. The precision voltage references on
the multiplexer are also checked to verify that the power to
the Mux is present and that the voltage references are within
tolerance.

Input Module Front Panel Indicators

Figure 3 shows the physical features of the RTD input
module. The front panel of each module contains status
indicators to display the operational status of the input
module and multiplexer.

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the
module. During normal operation the green ACTIVE
indicator flashes at the controller's scan rate. If a module
fault occurs the red FAULT indicator turns on and the green
ACTIVE indicator turns off.

MUX Fault Indicator

The red MUX FAULT indicator turns on when any of the
following fault conditions are detected:

·

No data received from the Mux.

·

Corrupted data from the Mux.

·

Unreasonable data values from the Mux.

Failure of the DC-to-DC converter supplying power to the
termination panel or the receiver circuitry can also result in a
MUX fault. Both of these faults are input module faults.