Specifications – Rockwell Automation T743x-xx ICS Regent+Plus RTD Input Equipment User Manual
Page 25
 
RTD Input Equipment (T7432)
 
P D - 7 0 3 7 M a r - 0 6  
25
points of failure and extend fault tolerance to include the 
RTDs. 
For additional safety considerations, please refer to the Safety 
Considerations section of the Regent User’s Guide. 
Specifications
Safetybus Power
1.8 load units
Number of Inputs
16, two, three, or four-wire 
RTDs 
RTD Input Types
American: 
European: 
100W Platinum 
"  = 0.00392 S/S/°C 
"  = 0.00385 S/S/°C 
RTD Units
Degrees Centigrade or 
degrees Fahrenheit 
RTD Resolution
Tenths or units
RTD Temperature Range
Normal Operation:
 
 
Over-Range:
 
 
Under-Range:
 
-200
°
to +800
°
C
(-328
°
to +1470
°
F)
+801
°
to +883
°
C
(+1471
°
to +1622
°
F)
-242
°
to -201
°
C
(-404
°
to --329
°
F)
Input Resolution
14-bit, 1 part in 16,384
Response Time
2 seconds, typical
Linearization
Automatic
Calibration
Automatic
Maximum Lead Resistance
 
20 ohms 
Current Source
1 mA (standard)
5 mA (optional)
Accuracy
T < 93
°
C (200
°
F)
T > 93
°
C (200
°
F)
 
+/- 0.55
°
C (1.0
°
F)
+/- 1.1
°
C (2.0
°
F)