2.3. Module Pinout Connections
Row
Pin
A
B
C
Description
1
2
50
Co-ax
10Base2 Ethernet 1
(fitted on T8151 up to build H and T8151B up to build B only)
3
4
Link 1
Connector Present Link - wire to A29
5
TXD1 (RS232)
Serial Port 1
6
RTS1 (RS232)
DTR1 (RS232)
RXD1 (RS232)
7
CTS1 (RS232)
DSR1 (RS232)
DCD1 (RS232)
8
BIO1 (RS485)
AIO1 (RS485)
RI1 (RS232)
9
BO1 (RS485)
AO1 (RS485)
GND1
10
11
TXD2 (RS232)
RTS2 (RS232)
RXD2 (RS232)
Serial Port 2
12
BIO2 (RS485)
AIO2 (RS485)
CTS2 (RS232)
13
BO2 (RS485)
AO2 (RS485)
GND2
14
15
BIO3 (RS485)
AIO3 (RS485)
GND3
Serial Port 3
16
BO3 (RS485)
AO3 (RS485)
GND3
17
18
BIO4 (RS485)
AIO4 (RS485)
GND4
Serial Port 4
19
BO4 (RS485)
AO4 (RS485)
GND4
20
21
TD+1
TD-1
10/100BaseT Ethernet 1
22
RD+1
RD-1
23
EARTH1
24
25
TD+2
TD-2
10/100BaseT Ethernet 2
26
RD+2
RD-2
27
EARTH2
28
29
LINK2
Connector Present Link - wire to C4
30
31
50
Co-ax
10Base2 Ethernet 2
(fitted on T8151 up to build H and T8151B up to build B only)
32
Table 3 External I/O Connector - Pin Out