Trusted, Communication interface t8151b – Rockwell Automation T8xxx Trusted Communications Interface User Manual

Page 25

Advertising
background image

Trusted

TM

Communication Interface T8151B

Issue 21 Apr 10

PD-T8151B

25

The following tables list the valid values for each of the control and status register types. In all cases
invalid values written to the control registers result in the inactive state being selected.

State

Value

Description

Inactive

0

Set link inactive, stop communications, set
slaves unavailable

Standby

1

Set link active but do not transfer data

Active

2

Set link active and transfer data

Table 4 Modbus Master Control register

State

Value

Description

Healthy

0

Link is active, no errors reported

Initialising

1

Link is not yet established or has failed,
slaves are unavailable

Error

2

Software error in communications module

Table 5 Modbus Master Status Register