3.5.7. Messages Tab

Figure 12 Modbus Slave Message Configuration

This panel lists all of the messages for the slave device in the order that the Modbus Master executes
them. Dragging and dropping a highlighted message anywhere in the list can be used to change the
order of the messages in the list.

To create a message to send to this slave, click ‘New’. (‘Insert’ adds a new message at the cursor
position, ‘New’ adds at the end).

Select a Message Type from the list. Depending on the address range and the number of addresses,
the appropriate Modbus command is used. The supported commands are shown below..

Address Range

Size

Direction

Modbus Command

Low

High

Type

Code

1

9999

1

Read

Read Coil Status (Read Coils)

0x01

1

9999

1

Write

Force single Coil (Write Coils)

0x05

1

9999

2 - 512

Read

Read Coil Status (Read Coils)

0x01

1

9999

2 - 512

Write

Force Multiple Coils (Write Coils)

0x15

10001

19999

1 - 512

Read

Read Input Status (Read Inputs)

0x02

30001

39999

1- 125

Read

Read Analogue Inputs (Read IP Registers)

0x04

40001

49999

1 - 125

Read

Read Holding register (Read Registers)

0x03

40001

49999

1

Write

Preset Single Register (Write Registers)

0x06

40001

49999

2 - 123

Write

Preset Multiple Registers (Write Registers)

0x16

Table 11 Modbus Message Types

The Variable Network Address is the Modbus address range of the variables as mapped in the
Trusted

TM

system. Only the starting address is needed; the end address is calculated automatically.

The Modbus Slave Address is the slave’s address range for the variables. Enter the start and end
addresses. The available address ranges and maximum number of addresses in a single message are
shown above.