Step 1. shut down the drive – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual
Page 34

2-22
GV3000/SE AC Drive ControlNet Network Communication Option Board
Step 1.
Step 1.1 Disconnect, lock out, and tag all incoming power to the drive.
Step 1.2 Wait five minutes for the DC bus capacitors to discharge.
Step 1.3 Remove the cover by loosening the four cover screws.
Important: Read and understand the warning labels on the inside of the drive before
Step 2.
Verify that the DC Bus Capacitors are Discharged
Step 2.1 Use a voltmeter to verify that there is no voltage at the drive’s AC input
power terminals (R/L1, S/L2, T/L3).
Step 2.2 Ensure that the DC bus capacitors are discharged. To check
a. Stand on a non-conductive surface and wear insulated gloves.
b. Use a voltmeter to measure the DC bus potential at the DC bus power
terminals as shown in figures 2.10 (15 to 25 HP) and 2.11 (25 to 60 HP).
Figure 2.10 – DC Bus Voltage Terminals (15 to 25 HP @ 460 VAC)
Motor Leads
AC Power
Input Leads
DC Bus
Volts
+
V/T2
U/T1
T/L3
S/L2
R/L1
W/T3
–