Troubleshooting

8-1

C

HAPTER

8

Troubleshooting

8.1

Diagnostic LEDs

The ControlNet Network Communication Option board has three bicolor (red/green)
LEDs. The Health LED indicates the status of the network communication board and
each of the two Communications LEDs indicates the status of its associated channel.

The Health LED provides the status of the network option board. It indicates whether
or not the board has power and is operating properly.

The Communications LEDs can be off, red, green, or some alternating pattern. In
table 6.2, the term “flashing” is used to describe LEDs that are always in the same
state, or in phase. The term “alternating” is used to describe LEDs that are always in
opposite states, or out of phase.

Table 8.1 – Health LED

LED State

Probable Cause

Recommended Action

Off

Power off

Turn power on.

Falshing
Red/Green

Device Test

None

Flashing
Green/Off

Incorrect node
configuration

Check network address and other
ControlNet configuration parameters

Steady Green

Normal operation

The network communication board is
configured correctly.

Flashing
Red/Off

Non-critical Fault

An invalid configuration is loaded.This
is the indication that no OS is loaded.

Steady Red

Critical Fault

The network communication board
has an unrecoverable fault.