Figure 5.17 - rslogix: attention symbol, Step 18. start rsnetworx and perform the following, A. click the on-line icon and browse the network – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual
Page 81: C. select file / save and save the project, D. close rsnetworx

Configuring ControlLogix Applications
5-9
Step 16. Select Communications / Download to download the configuration to the
controller (figure 5.16). RSLogix automatically enters on-line mode when
complete.
Step 17. An Attention symbol
is located next to the Node 2 (GV3000) icon in
figure 5.17, which indicates the ControlNet scanner needs to be configured.
Step 18. Start RSNetWorx and perform the following:
a. Click the On-line icon
and browse the network.
b. Select Edits Enabled and view the messages in the Message View for completion
(figure 5.18). The
icon should disappear from the nodes in the Graphical View.
c. Select File / Save and save the project.
d. Close RSNetworx.
This schedules the I/O that was configured in the RSLogix 5000.
Figure 5.16 – Download to the Controller Dialog Box
Figure 5.17 – RSLogix: Attention Symbol
Cnet_bridge: 0 (GV3000 2.1)