Table 4.6 - msg configuration information, Plc-5 configuration, Target device configuration – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual

Page 70: 2 about msg instruction timing, 3 about the files you can access

Advertising
background image

4-8

GV3000/SE AC Drive ControlNet Network Communication Option Board

To configure the MSG instruction, you must enter information about the data’s
location, size etc. Use table 4.6 to help you.

4.3.2 About MSG Instruction Timing

When a Typed Read message is sent to the drive, the response is sent to the PLC-5
programmable controller in under 20 msec. When a Typed Write message is sent to
the drive, the message is first processed by the drive. Therefore, 100-200 msec may
elapse before the response is returned to the PLC-5 programmable controller. These
times are applicable only when the network update time and unscheduled traffic
bandwidth are not limiting factors.

4.3.3 About the Files You Can Access

When you send an unscheduled message to the drive, the data table address you
specify for the target device determines what drive information you want to access.
The data table address is in the form of:

Nff:eee
where: N specifies the file type as integer, ff is the file number, and eee is the
element number (word).

The GV3000/SE ControlNet Option Board supports these file numbers:

N10 – Drive parameters (read and write)

N11 – Drive display data (read only)

N12 – Drive reference and feedback data (read and write)

N20 – Status of the most recent write parameter command (read only)

Table 4.6 – MSG Configuration Information

In this field:

Do this:

PLC-5 Configuration

Communication Command

To read information from the drive, enter PLC5
Typed Read.
To write data to the drive, enter PLC5 Typed Write.

Data Table Address

When reading information from the drive, enter the
file in which you want to store the data received
from the drive.
When writing information to the drive, enter the file
that will contain the data you want to send to the
drive.

Size in Elements

Enter the number of words to read or write. The
largest size you can use depends upon which file is
being accessed.

Port Number

Enter 2 to select ControlNet communication.

Target Device Configuration

Data Table Address

Enter the file in the drive where you want to read
data from or write data to. See section 4.3.3

ControlNet Path

Enter the node number of the drive.