PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Pre-Charge Connections on Drives with DC Input

You must connect the ASIC board connectors X9 and X15 to the X50
terminal block for the pre-charge circuit. The X50 terminal block is located
on the Control Frame. Refer to the Installation Instructions - PowerFlex
700S and 700H High Power Drives
, publication PFLEX-IN006

…,

for

information regarding the pre-charge circuit.

X50 Terminal Block Connections

Figure 9 Sample Pre-charge Wiring Diagram

ASIC Board Charge Relay Contact Ratings

ASIC Board
Connector

Terminal

to

X50 Terminal Pre-Charge Circuit Connection Description

X9

25

. . .

1

Pre-charge Complete Signal (+24V DC)

26

. . .

2

Pre-charge Complete Signal (Common)

X15

21

. . .

3

Charge Relay Contact

23

. . .

4

Charge Relay Contact

M

F2

R2 CR2

DC+

DC Source

DC-

CR2

R1

F1

M

Customer Connections - External precharge
circuitry is shown as dashed lines.

Drive Connections

Terminal Block

CR1

Pilot Relay

CR1

M

Main DC Contactor

M

CR2

Precharge

M

Precharge

Complete

1

2

3

4

25

26

21

23

X15

X9

ASIC Board

X50

Charge

Relay*

*Refer to the “ASIC Board

Charge Relay Contact

Ratings” table below.

Important: For DC Input Only.
Do Not Install on AC Input Drives

Load

Resistance load (cos

φ

= 1)

Rated load

8 A at 250 VAC: 5 A at 30 VDC

Rated carry current

8 A

Max. switching voltage

250 VAC; 30 VDC, (400 VAC)

Max. switching current

AC 8 A; DC 5 A

Max. switching power

2,000 VA; 150 W

Failure rate (reference value)

5 VDC 10 mA (for gold plating 0.35 µ min.)