PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Configuring the EMC Filter

Frame 11 size drives are equipped with common mode capacitors. To guard
against drive damage, these capacitors should be disconnected depending
upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground

If you are installing a 400/480V AC input drive on an ungrounded
distribution system or high resistive ground, you:

Must move the common mode jumper to the disconnected position -
refer to

Move the Common Mode Jumper to the Disconnected

Position on page 6

.

Should insulate terminal X4 on the Rectifier circuit board- refer to

Insulate Terminal X4 on the Rectifier Circuit Board on page 7

.

If you are installing a 600/690V AC input drive on an ungrounded
distribution system or high resistive ground, you:

Must move the common mode jumper to the disconnected position -
refer to

Move the Common Mode Jumper to the Disconnected

Position on page 6

.

Must insulate terminal X4 on the Rectifier circuit board- refer to

Insulate

Terminal X4 on the Rectifier Circuit Board on page 7

.

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

Must move the common mode jumper to the disconnected position -
refer to

Move the Common Mode Jumper to the Disconnected

Position on page 6

.

Must insulate terminal X4 on the Rectifier circuit board- refer to

Insulate

Terminal X4 on the Rectifier Circuit Board on page 7

.

Note:

Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives - Installation Instructions
,
publication DRIVES-IN001…, for additional information on an
ungrounded distribution system or high resistive ground
installation.