Issue 1, March, 06
DC digital input modules provide input sensing for 16 field 
input switches. Three types of modules are available for 
interfacing to inputs powered from 24, 48, or 120 VDC field 
power supplies. Each module's triplicated I/O Safetybus 
interface ensures that no failure in the module can affect the 
operation of the Regent system or other I/O modules in the 
system. Extensive fault detection and annunciation of critical 
redundant circuits help prevent the controllers from receiving 
erroneous data from a faulty input module. 
Features
·
Sixteen input circuits, configured as two isolated groups of
eight circuits each.
·
Fault tolerant operation when connected in parallel with
redundant modules of the same type.
·
Hot-replaceable.
·
Automatic self-testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
Individual front panel indicators on each module show active
and fault status and logic-side input on/off status.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5.
Three DC digital input modules can be connected in parallel 
to obtain fault tolerant input sensing. In this triple module 
configuration, a failed module can be removed and replaced 
without interrupting the input signals.