Rockwell Automation T3408 ICS Regent DC Digital Input Modules User Manual

Page 16

Advertising
background image

DC Digital Input Modules (T3401, 02, and 08)


1 6

Industrial Control Services

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

ANSI/IEEE C37.90 - Surge

Withstand Capability


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
2.5 kV damped 1 MHz sine
wave
4 kV bi-directional impulse,
10 nsec rise time, fast
transient (

T3402, T3408 only

)

Safety

Certified to DIN V VDE
0801 for Risk Class 5. Also
designed to meet UL 508 and
CSA 22.2, No. 142-M1981

Dimensions

Height:

Width:

Depth:


12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)

Weight

3.0 lbs (1.4 kg)