Specifications – Rockwell Automation T3408 ICS Regent DC Digital Input Modules User Manual

Page 15

Advertising
background image

(T3401, 02, and 08) DC Digital Input Modules


P D - 6 0 1 1 M a r - 0 6

15

Specifications

Safetybus Power

1.15 load units

Number of Inputs

16 circuits divided into two
groups of eight

T3401

T3402

T3408

Voltage Range

14 to 30 VDC

38 to 58 VDC

95 to 150 VDC

Turn-On Voltage

12 VDC, min

36 VDC, min

88 VDC, min

Turn-Off Voltage

4.7 VDC, max

11 VDC, max

28 VDC, max

Input Current

8.7 mA

4.4 mA

4.4 mA

Turn-On Delay

minimum

maximum

0.2 msec

1.8 msec

0.1 msec

1.0 msec

0.05 msec

0.4 msec

Turn-Off Delay

minimum

maximum

0.5 msec

2.6 msec

0.15 msec

1.0 msec

0.05 msec

0.5 msec

Over Voltage
Protection

continuous:

burst:

50 VAC

80 VAC, for
5 sec

140 VAC

220 VAC, for 5
sec

400 VAC

880 VAC, for
5 sec

Heat
Dissipation

10 Watts,

34 BTUs/hour

9.5 Watts,

32 BTUs/hour

18 Watts,

60 BTUs/hour

Fusing

None, fuse external if
required

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (input
group 1-8 to input group
9-16)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Advertising