Rockwell Automation T3408 ICS Regent DC Digital Input Modules User Manual
Page 7
 
(T3401, 02, and 08) DC Digital Input Modules
 
P D - 6 0 1 1 M a r - 0 6  
7
installed. Each terminal block consists of ten #6 wire clamp 
screw terminals, with each terminal capable of holding two 12 
AWG wires. 
The module has a separate common power return terminal for 
each group of inputs (group 1: channels 1-8, group 2: channels 
9-16). These two groups are electrically isolated from each 
other (2500 volts minimum). Figure 5 shows the proper 
connection of input signals to the input wiring terminals. 
When redundant field sensors are installed, each input 
module is wired as shown in Figure 5. In a fault tolerant 
configuration with single field sensors, the input signals are 
connected in parallel across all three input modules as shown 
in Figure 6.