Maintenance, Safety considerations – Rockwell Automation T3408 ICS Regent DC Digital Input Modules User Manual
Page 13
 
(T3401, 02, and 08) DC Digital Input Modules
 
P D - 6 0 1 1 M a r - 0 6  
13
Figure 10. Programming Fault Tolerant Digital Inputs.
In this illustration, VOTE_A_NAME, VOTE_B_NAME, and 
VOTE_C_NAME represent the three digital inputs to be two-
out-of-three voted. ERROR_A_NAME, ERROR_B_NAME 
and ERROR_C_NAME are the error bits for the digital 
inputs. RESULT_NAME is the result of the voter instruction. 
The field Msec is the time, in milliseconds, an input can be 
incorrect before signaling an error. RESET_NAME is the 
reset bit used to reset the latched error bits. 
The voter instruction can be used to vote digital input points 
or entire digital input modules. When voting digital input 
modules, the tag names VOTE_A_NAME, VOTE_B_NAME, 
and VOTE_C_NAME would be the names of the digital input 
modules and RESULT_NAME would be a shared variable 
register. After voting the modules, a block move instruction 
should be used to move the contents of the register 
RESULT_NAME into individual shared variable control 
relays. Refer to the W
INTERPRET
Help files for more
information about the block move instruction and shared 
variable definitions. 
Maintenance
No periodic maintenance or calibration is required for the 
digital input modules. There are no user replaceable parts 
inside these modules. In safety critical input applications, the 
inputs should be dynamically transitioned at a period not 
greater than six months. 
Safety Considerations
The DC voltage digital input modules are TÜV certified as