Assigning security codes to hmi tags, Assigning security codes to – Rockwell Automation FactoryTalk View Site Edition Users Guide User Manual

Page 101

Advertising
background image

5

S

ETTING

UP

SECURITY

5–19

• •

5 • Pl

aceh

ol

der

2. Right-click the OLE object, select Animation > OLE Verb.

3. In the OLE Verb tab, select the verb that you want to secure.

4. In the Security list, select a security code other than the asterisk ( * ) .

5. Click Apply.

Assigning security codes to HMI tags

In the Tags editor, you can set up security for an HMI tag, to prevent users from writing to
the tag.

Only users or groups assigned the tag’s security code, will be able to change the tag’s
value at run time. Users must have at least one security code assigned, to change the value
of tags assigned an asterisk ( * ) .

To assign security to an HMI tag

1. In FactoryTalk View Studio, in the Explorer window, right-click the Tags icon, and

then click Open.

2. In the Tags editor, select the HMI tag that you want to secure.

You cannot assign a security codes to data server tags. To prevent users from changing the
value of a data server tag, map its address to an HMI tag, and then secure the HMI tag.

Select a
security code.

Advertising