Include extended information in the server cache file

Select this check box to make available additional information about tags, for example,
their data types, when you are not connected to the data server.

To create a data server cache

1. To provide the list of tags, ensure that the OPC data server is running, and that the

devices are connected.

2. In the Advanced tab of the OPC Data Server Properties dialog box, select the check

box, Include extended information in the server cache file.

3. Click Create Cache, and then click OK.

Synchronizing a data server’s cache

If tags are added, modified, or deleted on the data server, you must synchronize the cache
manually. You can synchronize a data server’s cache only after you have created one.

To synchronize a data server’s cache

1. To provide the list of tags, ensure that the OPC data server is running, and that the

devices are connected.

2. In FactoryTalk View Studio, in the Explorer window, right-click the data server, and

then click Properties.

3. In the Advanced tab of the OPC Data Server Properties dialog box, click

Synchronize, and then click OK.